DIRECT DIGITAL READOUT IN ENGLISH AND METRIC UNITS |
AIR VELOCITY:
Accuracy with standard pitot tube is ±3% of reading ± 7 fpm 50 to 5,000 fpm pitot tube (30,000 fpm FS). |
DIFFERENTIAL PRESSURE:
±2% of reading ± 0.001 in wc from 0.0500 to 50.00 in wc, (0.0001 to 60 in wc FS); 20 psid safe pressure. |
TEMPERATURE:
±0.5℉ accuracy from 32℉ to 158℉. |
AIR FLOW:
Accuracy is ±3% of reading ±7 cfm from 100 to 2000 cfm; range is 25 to 2500 supply, 25 to 1500 exhaust with 8400 FlowHood. |
ABSOLUTE PRESSURE:
±2% of reading ±0.1 in Hg from 14 to 40 in Hg referenced to vacuum. 60 psia maximum safe pressure. |
AMBIENT RANGE:
Full range compensation from 40℉ to 140℉. |
AIR DENSITY CORRECTION:
Local or standard (mass flow) air density correction range is 14 to 40 in Hg and 32℉ to 158℉. |
POSITION SENSITIVITY:
Unaffected by position. |
CALIBRATION:
Calibration certified NIST traceable. |
READOUT:
10 digit, 0.4", high contrast, liquid crystal display. |
METER HOUSING:
High impact, molded, "T" grade ABS. |
METER WEIGHT:
36 ounces (1.02kg), including batteries |
SIZE:
6.0" x 6.4" x 2.7" (15.2 x 16.3 x 6.9 cm) |
CONNECTIONS:
1/4" OD slip-on for 3/16" ID soft tubing. |
BATTERY LIFE:
3000 readings per charge, 500 recharge cycles. |
|